|
How
are ATCO's pressure ratings determined?
Atco's UL Listed pressure ratings are determined by testing
duct in straight lengths, at ambient temperatures. Testing is done
in a static condition (no airflow). The test sample is sealed airtight
on both ends and pressurized to 2 ½ times the manufacturers
desired rated pressure for a test period of one hour. A minimum
of 1 1/4" of positive pressure must be achieved in order to
pass the test.
Atco performs
some additional tests in accordance with the Air Diffusion Council,
FD 72-R1 Flexible Duct Test Code. The purpose of these tests is
to simulate a variety of realistic conditions, which may exist in
actual installations. The ADC tests include a 90 degree bend, heated
air at continuous and intermittent temperatures, for a test period
of 168 hours. The resulting "Recommended Operating Pressures"
are intended to give the contractor and/or engineer a responsible
guideline within which to design the duct system.
What
are ATCO's pressure ratings?
These are ratings for our standard products:
Rated Positive Pressure:
10” w.g. per UL 181
Recommended Operating Pressures:
6” w.g. pos., 4”-12” dia., 4”w.g. pos.,
14”-20” dia.; ¾” neg., all dia.
Velocity:
5,000 FPM
Flame Spread/ Smoke Developed:
25 max/ 50 max
Standard Lengths:
25’

What is the thickness of ATCO's insulation?
Atco provides insulated flex duct with three different R-Values
(4.2, 6.0, and 8.0). The thickness of each is:
R-4.2 = 1 ¼”  C-Value
of Approx: 0.238
R-6.0 = 2” 
C-Value of Approx: 0.167
R-8.0 = 2 ½”  C-Value
of Approx: 0.125
All Density = ¾ lb
All fiberglass insulation is supplied by Owens Corning.
In an attempt
to standardize, the flexible duct industry no longer states insulation
values in thickness and density. The Air Diffusion Council, an industry
organization of manufacturers, certifies R-Values based on insulation
only, at installed wall thickness, based on ASTM C-518. Underwriters
Laboratories classifies these tested R-Values based on plant inspections.
These two third party verifications provide an accurate and reliable
method of assuring that you are getting the thermal performance
that you require.

Can Flexible Duct
be exposed to ultraviolet sunlight?
No, flexible duct must be protected from the weather, including
sunlight. In the late 1980’s, manufacturers of insulated flexible
duct discovered that the products with gray polyester jackets could
fail when exposed to direct or indirect sunlight. The ultraviolet
rays in the sunlight would break the chemical bonds in the gray
polyester jackets causing them to disintegrate over a period of
several years. To alleviate the problem, manufactures began using
black polyester jackets and metallized polyester jackets. The carbon
black used to color the black polyester jackets has an inherent
resistance to ultraviolet light as so is the metallized polyester.
Since the change, the problem has been eliminated. However, most
manufacturers still require that insulated flexible duct of any
type not be installed in areas with direct or indirect sunlight.
We are confident of the quality of our flexible duct products.
If you have a duct that will be exposed to Ultraviolet light from
the use of a Bio-treatment lamp or UV lamp, we suggest you use our
NEW Ultra-Flex Duct Kit.
It is specifically designed to be used where UV light from a Bio-treatment
lamp is emitted onto the core of a non-metallic flexible duct.

Does
ATCO have an "acoustical duct"?
Atco does not have a duct specially designed to reduce noise within
the duct system. However, Atco does have independent test data on
the acoustical properties of our standard products. The data shows
Net Insertion Loss on 10' lengths of different diameters of Atco
duct, as compared to sheet metal duct. Tests were done on straight
lengths, and duct with a 90 degree bend, with and without airflow,
and are recorded at a variety of octave bands. Click here
to download the acoustical information on our products.

Does
ATCO have a plenum rated duct?
There is no “plenum rated flexible duct” to the best
of our knowledge. As far as we know, UL 181 Class 1 Air Duct listing
will satisfy the requirements for a plenum rated ceiling. As always,
local jurisdictions have final say.
How does
duct condensation or “sweating” occur?
Condensation or “sweating” is a complex problem that
is primarily seen in high humidity areas. There are a large number
of factors that can lead to condensation. Condensation occurs on
any surface that is colder than the wet bulb temperature of the
air surrounding it. In air ducts it is most common to see this on
the outer vapor barrier of the duct. However, it can also be on
the inner core in flexible ducts, or the sheet metal of a sheet
metal system. We also see condensation at the fittings or plenums.
Any place where the temperature of a surface is colder than the
wet bulb temperature of the surrounding air you will have condensation.
To prevent
sweating it is necessary to either raise the temperature of the
sweating surface, or lower the wet bulb temperature of the air.
It is usually easiest to increase the temperature of the sweating
surface by adding insulation. However by increasing ventilation
it may be possible to lower the wet bulb temperature of the air.
When it is
necessary to route an insulated duct through a truss/joist support,
care should be taken to prevent tearing of the vapor barrier and
insulation.
If localized
compression occurs, a 20% diametric compression of the duct core
at the truss/support will result in only an approximate 5% change
in cross-sectional area of the duct. This is little change compared
to oval ducts, which are commonly used in HVAC applications.
In an insulated
flex duct, much of the visible compression is actually compression
of the fiberglass. Such localized compression of the fiberglass
should have minimal, negative effect on the total, thermal losses
of the duct. However, when the installation is in a critical condensation
zone, localized compression could result in localized sweating.
The A/C contractor
or designer should consider this information in view of total design
performance. Also, be advised the local authority having jurisdiction
will have the final say in these matters

Has ATCO’s products been
tested for mold growth and humidity?
All UL 181 Air Ducts and Connectors have been tested by Underwriters
Laboratories, Inc. for mold growth and humidity, and are considered
by the manufacturer as acceptable for use in conjunction with evaporative
coolers. Please refer to section 3 Testing, Listing, Reporting and
Certifying of the ADC Flexible Duct Performance & Installation
Standards (Greenbook) www.flexibleduct.org
for further information.

What
is the difference between Air Ducts and Air Connectors?
UL (Underwriters Laboratories), in their 181 Standard for Factory-Made
Air Ducts and Air Connectors, defines two categories of flexible
"ducts".
The UL Listed
Air Duct must pass all of the tests in the UL 181 Standard. Air
Ducts are labeled with a square or rectangular shaped label showing
their respective listing. There is no limitation on the length of
runs when using UL Listed Air Ducts.
The UL Listed
Air Connector must pass only a limited number of the UL 181 tests,
and is labeled with a round shaped label, which states "for
installation in lengths not over 14 feet".

Can
our UL 181 Class I Air Connector UPC #050 be used for dryer venting?
No, it is not approved
by UL for dryer venting. We do NOT have a product that
is a UL approved Dryer Venting product.
What
materials are required/allowed to be used when hanging or supporting
flexible duct?
For ATCO’s Installation Instructions, click here.
When hanging or supporting flexible duct, there are a number of
different materials which are used regionally. Atco doesn't specify
a particular material in our Installation Instructions, however
Atco and the Air Diffusion Council do make the following statement:
"Hanger or saddle material in contact with the flexible duct
shall be of sufficient width to prevent any restriction of the internal
diameter of the duct when the weight of the supported section rests
on the hanger or saddle material. In no case will the material contacting
the flexible duct be less than 1 1/2" (38 mm) wide". As
in all cases, local jurisdiction has final say in these matters.

Can screws be used to fasten
flexible duct core?
ATCO Rubber Products does not recommend screws be used to fasten
the polyester core of the air ducts because they weaken the polyester.
Polyester is a very strong material as long as there are no holes
or tears in it. As soon as a tear or hole is introduced, it’s
strength drops. To maintain our UL approval status, our air ducts
must pass a tension test (25 pounds hanging from one end of the
duct), a torsion test (one end rotated 180° or to 25 foot-pounds
whichever comes first) and then a leakage test. In all of these
tests, both ends must be connected to collars per our installation
instructions. Flexible duct connected with screws would not pass
these tests.
|